ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407531

Federal Type:

C

Water System Name:

EPCOR - NORTH EAST AGUA FRIA

Primary Source:

GW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

2005-07-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
22I2596-01IOC 1074 ANTIMONY, TOTAL 2022-09-22 EPDS001 < MRL 0.0005  .006 MG/L 2022-01-01
2024-12-31
22I2596-01IOC 1005 ARSENIC 2022-09-22 EPDS001 .0066  MG/L .01 MG/L 2022-07-01
2022-09-30
22I2596-01IOC 1010 BARIUM 2022-09-22 EPDS001 .052  MG/L 2 MG/L 2022-01-01
2024-12-31
22I2596-01IOC 1075 BERYLLIUM, TOTAL 2022-09-22 EPDS001 < MRL 0.002  .004 MG/L 2022-01-01
2024-12-31
22I2596-01IOC 1015 CADMIUM 2022-09-22 EPDS001 < MRL 0.0001  .005 MG/L 2022-01-01
2024-12-31
22I2596-01IOC 1020 CHROMIUM 2022-09-22 EPDS001 < MRL 0.005 MG/L .1 MG/L 2022-01-01
2024-12-31
22I2596-01IOC 1024 CYANIDE 2022-09-22 EPDS001 < MRL 0.01  .2 MG/L 2022-01-01
2024-12-31
22I2596-01IOC 1025 FLUORIDE 2022-09-22 EPDS001 < MRL 0.5 MG/L 4 MG/L 2022-01-01
2024-12-31
22I2596-01IOC 1035 MERCURY 2022-09-22 EPDS001 < MRL 0.0002 MG/L .002 MG/L 2022-01-01
2024-12-31
22I2596-01IOC 1036 NICKEL 2022-09-22 EPDS001 < MRL 0.02  2022-01-01
2024-12-31
22I2596-01IOC 1040 NITRATE 2022-09-22 EPDS001 1.24  MG/L 10 MG/L 2022-01-01
2022-12-31
22I2596-01IOC 1038 NITRATE-NITRITE 2022-09-22 EPDS001 1.24  MG/L 10 MG/L
22I2596-01IOC 1041 NITRITE 2022-09-22 EPDS001 < MRL 0.25  1 MG/L 2016-01-01
2024-12-31
22I2596-01IOC 1045 SELENIUM 2022-09-22 EPDS001 < MRL 0.002  .05 MG/L 2022-01-01
2024-12-31
22I2596-01IOC 1052 SODIUM 2022-09-22 EPDS001 48  MG/L 3000 MG/L 2022-01-01
2024-12-31
22I2596-01IOC 1085 THALLIUM, TOTAL 2022-09-22 EPDS001 < MRL 0.0005 MG/L .002 MG/L 2022-01-01
2024-12-31