ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0408701

Federal Type:

C

Water System Name:

KATHERINE LANDING DWTP

Primary Source:

SW

Principal County Served:

MOHAVE

System Status:

A

Comments:

Activity Date:

1972-01-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
98-0768 1074 ANTIMONY, TOTAL 1998-11-05 EPDS001 < MRL 0.003 MG/L .006 MG/L
98-0768 1005 ARSENIC 1998-11-05 EPDS001 .002  MG/L .01 MG/L
98-0768 1010 BARIUM 1998-11-05 EPDS001 .294  MG/L 2 MG/L
98-0768 1015 CADMIUM 1998-11-05 EPDS001 .0001  MG/L .005 MG/L
98-0768 1020 CHROMIUM 1998-11-05 EPDS001 < MRL 0.001 MG/L .1 MG/L
98-0768 1025 FLUORIDE 1998-11-05 EPDS001 .26  MG/L 4 MG/L
98-0768 1040 NITRATE 1998-11-05 EPDS001 .13  MG/L 10 MG/L
98-0768 1041 NITRITE 1998-11-05 EPDS001 < MRL 0.01 MG/L 1 MG/L
98-0768 1045 SELENIUM 1998-11-05 EPDS001 < MRL 0.002 MG/L .05 MG/L
98-0768 1052 SODIUM 1998-11-05 EPDS001 66.4  MG/L 3000 MG/L
98-0768 1055 SULFATE 1998-11-05 EPDS001 190  MG/L 250 MG/L