Water System Detail Information |
Water System No.: |
AZ0407128 |
Federal Type: |
C |
Water System Name: |
ARIZONA WATER CO - WHITE TANKS |
Primary Source: |
SWP |
Principal County Served: |
MARICOPA |
System Status: |
A |
Comments: |
|
Activity Date: |
1977-06-01 |
Sample Number |
Analyte Code |
Analyte Name |
Date |
Sample Point |
Less Than Ind. |
Level Type |
Reporting Level |
Concentration |
MCL |
Compliance Monitoring Period |
21D2883-01IOC |
1074 |
ANTIMONY, TOTAL |
2021-04-21 |
EPDS001 |
< |
MRL |
0.0005 MG/L |
|
.006 MG/L |
2021-01-01
2023-12-31
|
21D2883-01IOC |
1005 |
ARSENIC |
2021-04-21 |
EPDS001 |
|
|
|
0.0036 MG/L |
.01 MG/L |
2021-04-01
2021-06-30
|
21D2883-01IOC |
1010 |
BARIUM |
2021-04-21 |
EPDS001 |
|
|
|
0.29 MG/L |
2 MG/L |
2021-01-01
2023-12-31
|
21D2883-01IOC |
1075 |
BERYLLIUM, TOTAL |
2021-04-21 |
EPDS001 |
< |
MDL |
0.002 MG/L |
|
.004 MG/L |
2021-01-01
2023-12-31
|
21D2883-01IOC |
1015 |
CADMIUM |
2021-04-21 |
EPDS001 |
< |
MRL |
0.0001 MG/L |
|
.005 MG/L |
2021-01-01
2023-12-31
|
21D2883-01IOC |
1020 |
CHROMIUM |
2021-04-21 |
EPDS001 |
|
|
|
0.014 MG/L |
.1 MG/L |
2021-01-01
2023-12-31
|
21D2883-01IOC |
1035 |
MERCURY |
2021-04-21 |
EPDS001 |
< |
MRL |
0.0002 MG/L |
|
.002 MG/L |
2021-01-01
2023-12-31
|
21D2883-01IOC |
1036 |
NICKEL |
2021-04-21 |
EPDS001 |
< |
MRL |
0.02 MG/L |
|
|
2021-01-01
2023-12-31
|
21D2883-01IOC |
1045 |
SELENIUM |
2021-04-21 |
EPDS001 |
|
|
|
0.0034 MG/L |
.05 MG/L |
2021-01-01
2023-12-31
|
21D2883-01IOC |
1052 |
SODIUM |
2021-04-21 |
EPDS001 |
|
|
|
65 MG/L |
3000 MG/L |
2021-01-01
2023-12-31
|
21D2883-01IOC |
1085 |
THALLIUM, TOTAL |
2021-04-21 |
EPDS001 |
< |
MRL |
0.0005 MG/L |
|
.002 MG/L |
2021-01-01
2023-12-31
|
|