Deficiencies/Recommendations |
Category |
Severity |
Description Code Description Text |
Comments |
Determine Date |
Resolved Date |
FW |
MIN |
|
The overflow pipes for the storage tanks do not extend towards the ground 12-24 inches above ground. |
02-27-2018
|
05-01-2018
|
SE |
MIN |
|
System does not have a proper 6-foot tall security fence installed around the two storage tanks. |
02-27-2018
|
05-01-2018
|
FW |
MIN |
|
The storage tanks do not have proper air vents installed on them. |
02-27-2018
|
05-01-2018
|
SO |
MIN |
|
#16 mesh screen placed on well vent is plastic material and needs to be made of metal.
|
02-27-2018
|
05-01-2018
|
FW |
MIN |
|
#16 mesh screen placed on storage tank vent is plastic material and needs to be made of metal.
|
02-27-2018
|
05-01-2018
|
FW |
MIN |
|
No concrete slabs beneath storage tank overflow pipes to prevent erosion. |
02-27-2018
|
05-01-2018
|
FW |
MIN |
|
Soil and brush on side of one of the storage tanks. |
02-27-2018
|