Failure to install proper well vent - Install a well vent 2 ft above grade, elbowed down, screened/covered with #16 mesh screen.
02-07-2022
03-03-2022
SO
MIN
1 -1
Failure to install proper well vent - Install a well vent 2 ft above grade, elbowed down, screened/covered with #16 mesh screen.
02-07-2022
03-03-2022
SO
MIN
1 -1
Failure to install proper well vent - Install a well vent 2 ft above grade, elbowed down, screened/covered with #16 mesh screen.
02-07-2022
03-03-2022
FW
MIN
Failure to install a proper storage tank vent - Install a storage tank vent with an inverted "u" configuration and screen openings with 16-mesh screen, Vent can be installed on roof hatch cover.