Parties Present
Name Organization Phone Number
ADDINGTON, JAMES W 602-329-4845
GEBREMARIAM, RESHET ADEQ 602-771-4220


Deficiencies/Recommendations
Category Severity Description Code
Description Text
Comments Determine
Date
Resolved
Date
SE MIN 106 -Release Point Access to the well is not restricted. 06-29-2017
SM MIN Nitrate and Nitrite samples are currently being taken at 5322 60-Point at a sample tap right after storage tank 2, which is in the distribution system (this sample tap is used to fill water bottles etc. by people using the range). 06-29-2017
SE MIN Storage tank 1, storage tank 2 and storage tank 4 are not enclosed by security fencing. 06-29-2017
FW MIN The four storage tanks do not have drains and overflow pipes. 06-29-2017