Deficiencies/Recommendations |
Category |
Severity |
Description Code Description Text |
Comments |
Determine Date |
Resolved Date |
SO |
MIN |
1 ->=1:500
|
Wells 55-627291 and 55-507674 do not have air vents installed along with #16 non-corrodible mesh screens. |
03-28-2018
|
11-26-2018
|
FW |
MIN |
102 -Facility Center/Centroid
|
There is brush and soil along sides of the storage tank, leading to corrosion of the tank itself. |
03-28-2018
|
07-20-2018
|
SO |
MIN |
1 -1
|
Wells 55-627291 and 55-507674 do not have air vents installed along with #16 non-corrodible mesh screens. |
03-28-2018
|
11-26-2018
|
SO |
MIN |
1 -1
|
Wells 55-627291 and 55-507674 do not have air vents installed along with #16 non-corrodible mesh screens. |
03-28-2018
|
11-26-2018
|
SO |
MIN |
|
Well 55-507674 has severe cracks throughout the slab. |
03-28-2018
|
11-08-2018
|
DS |
MIN |
|
There is a standpipe with a hose attached used to fill fire fighting trucks with no sign of an air gap or approved backflow prevention device. |
03-28-2018
|
11-08-2018
|
SO |
MIN |
|
Well house 55-507674 has a presence of fecal matter from mice. |
03-28-2018
|
07-20-2018
|