Deficiencies/Recommendations |
Category |
Severity |
Description Code Description Text |
Comments |
Determine Date |
Resolved Date |
SO |
MIN |
2 -Between 1:500 and 1:5,000
|
One of the well's air vents needs a smaller #16 non-corrodible screen. |
11-18-2016
|
12-07-2016
|
FW |
MIN |
8 -Between 1:50,000 and 1:100,000
|
The flapper on the overflow pipe of the storage tank doesn't completely shut and needs to be screened. |
11-18-2016
|
12-07-2016
|
SO |
MIN |
2 -2
|
One of the well's air vents needs a smaller #16 non-corrodible screen. |
11-18-2016
|
12-07-2016
|
TR |
MIN |
|
System is using commercial bleach from Shamrock Foods, which doesn't conform to ANSI/NSF Standard 60. |
11-18-2016
|
|