Deficiencies/Recommendations |
Category |
Severity |
Description Code Description Text |
Comments |
Determine Date |
Resolved Date |
SO |
REC |
108 -Other
|
Failure to provide a check valve on the discharge line. |
10-31-2019
|
11-01-2019
|
DS |
REC |
|
Failure to provide a shut off valve on the discharge line. |
10-31-2019
|
11-01-2019
|
FW |
REC |
|
Failure to mount booster pumps on a concrete foundation. |
10-31-2019
|
11-01-2019
|
PU |
REC |
|
Per engineering Bulletin No. 10, Chapter 3, Section C.1. TYPE AND NUMBER OF PUMPS
A minimum of two (2) complete pumping units shall be provided, each capable of delivering the
required flow while maintaining minimum pressures. |
10-31-2019
|
11-01-2019
|
DS |
REC |
|
Pressure gauge is not functioning. |
10-31-2019
|
11-01-2019
|