Water System Detail Information

Water System No.:

AZ0403011

Federal Type:

C

Water System Name:

HECKETHORN WATER COMPANY

Primary Source:

GW

Principal County Served:

COCONINO

System Status:

A - MAP

Comments:

Activity Date:

06-01-1977





Parties Present
Name Organization Phone Number
LESKO, WILLIAM F 928-779-0543
SCHOEN, STEVEN ADEQ 602-771-4475


Deficiencies/Recommendations
Category Severity Description Code
Description Text
Comments Determine
Date
Resolved
Date
SO MIN 1 ->=1:500 1. Because of winter insulation, not able to verify that well vent turn down and terminates 2 feet above the slab and is protected with a #16 no corrosive mesh screen 01-12-2017 08-17-2017
FW MIN 8 -Between 1:50,000 and 1:100,000 4. Was not able to verify if storage tank 001 (6000 gallons) overflow discharge point was protected by #16 non- corrosive mesh screen and was between 12 and 24 inches from the ground. 01-12-2017 08-17-2017
SO MIN 1 -1 1. Because of winter insulation, not able to verify that well vent turn down and terminates 2 feet above the slab and is protected with a #16 no corrosive mesh screen 01-12-2017 08-17-2017
SO MIN 1 -1 1. Because of winter insulation, not able to verify that well vent turn down and terminates 2 feet above the slab and is protected with a #16 no corrosive mesh screen 01-12-2017 08-17-2017
FW MIN 3. Was not able to verify if storage tank 001 (6000 gallons) had a vent and was protected with a #16 non-corrosive mesh screen. 5. Was not able to verify that storage tank 002 (10,000 gallon) had a vent and was protected with a #16 non-corrosive mesh screen. 6. Was not able to verify that storage tank 003 (40,000 gallons) had a vent and was protected by a #16 non-corrosive mesh screen. 01-12-2017 08-17-2017
SO MIN 2. Because of winter insulation, was not able to verify that well seal was in good condition. 01-12-2017 08-17-2017
FW MIN 7. Hatch on storage tank 003 (40,000 gallon) was not secured with a lock. 01-12-2017 08-17-2017
SM MIN Drinking water system does not have a Cross Connection/Backflow Prevention Plan that requires all backflow assembles in the system to be tested annually and the records be kept on site for at least 3 years. 01-12-2017 08-17-2017