ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0420478

Federal Type:

C

Water System Name:

SILVER CHOLLA MHP

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

06-01-1977





Parties Present
Name Organization Phone Number
GOMEZ, RENE PDEQ 520-724-7365


Deficiencies/Recommendations
Category Severity Description Code
Description Text
Comments Determine
Date
Resolved
Date
SO MIN 1 ->=1:500 Engineering Bulletin No. 10 Chapter 3, G 2 Well Vent All wells shall be equipped with a vent which shall terminate at least 2 feet above the protective slab, and which shall be covered with a number 16 mesh screen. 08-11-2022 10-12-2022
SO MIN 1 -1 Engineering Bulletin No. 10 Chapter 3, G 2 Well Vent All wells shall be equipped with a vent which shall terminate at least 2 feet above the protective slab, and which shall be covered with a number 16 mesh screen. 08-11-2022 10-12-2022
SO MIN 1 -1 Engineering Bulletin No. 10 Chapter 3, G 2 Well Vent All wells shall be equipped with a vent which shall terminate at least 2 feet above the protective slab, and which shall be covered with a number 16 mesh screen. 08-11-2022 10-12-2022
SO MIN Engineering Bulletin No. 10 Chapter 2, E.9 Sanitary Well Seal and Slab A slab shall be provided around all wells. The slab should extend a minimum of 3 feet from the center of the well, be a minimum of 6 inches thick, and slope away from the well a minimum of 1/4? per foot. 08-11-2022 10-04-2022
SO REC Snakes, rodents and insects that dwell in debris and excess vegetation can carry contaminants and diseases that could seep into a well during precipitation events. 08-11-2022 10-04-2022