SO |
SIG |
|
ISSUE DESCRIPTION
This facility needs to be reclassified from a Ground water source to Ground water under direct influence of surface water (GUDI). This facility is treating the spring as a GUDI by adding T-Floc for coagulation and allows 70 minutes of contact time through 3 baffled tanks. The water is then pushed through two pressure filters filled with a black media possibly Granulated Activated Carbon. The system disinfects with liquid sodium hypochlorite. If the spring is a GUDI the source would not have been sampled, triggering a level 2 assessment.
CORRECTIVE ACTION TO BE TAKEN
Start collecting turbidity and Maximum Disinfection Residual Levels (MRDLs). Start taking source water turbidity, temperature, & pH, to determine the proper dosing levels for coagulant addition. Report to ADEQ. Additional correspondence forthcoming.
|
07-20-2016
|
06-21-2016
|