TR |
REC |
|
Deficiency: Failure to provide a hypo-chlorinator as a means to disinfect the water.
Technical Basis: Engineering Bulletin No.8 R9-8-210 GENERAL POLICY, PARAGRAPH B. All public and semi-public water systems shall obtain water from an approved source or sources¿ if water from any source is subject to contamination, adequate purification, disinfection, or both shall be carried out..
Recommendations:Install a hypo-chlorinator at the well to adequately provide a continuous free chlorine residual of 0.2 mg/l to 1.0 mg/l throughout the distribution system. |
05-07-2020
|
|