The POU treatment devices throughout the public water system are not NSF-61 approved for the treatment of nitrates and have insufficient pressure to function properly.
07-20-2018
08-31-2018
OC
SIG
Current designated operator does not have a grade one water treatment certification for the public water system.
07-20-2018
11-16-2018
SO
MIN
The raw water sample tap is not turned down and has threads installed on it at the well.