OT |
SIG |
|
Initial positive likely due to failed chlorine pump (overheat and bubble lock, had just replaced foot valve). New injector site overwhelmed by new bladder tank pressure in well house.
Well head has possible breaches at conduit on well head (spilt top) and small cracks on concrete base around well head.
Repeat positives likely due to well head and chlorine low residual.
8/9 - Positive Coliform
8/11- GW Repeats Drawn - All Positive Coliform
8/12 - Pull chlorine injector (clean) & reseat and flushing of system; acquire residual within distribution |
09-02-2022
|
09-02-2022
|