OT |
SIG |
|
The July routine sample was taken on 7/18/2023 and results were TC+/EC-. TC+ result was due to inadequate contact time for the 12.5% sodium hypochlorite solution. The system had been treated that morning at roughly around 0700 and the sample was collected at 1025. Repeat samples were not collected within the 24 hour window. Repeat samples were collected on 8/29/2023 with results of TC-/EC-, however the Well sample was TC+/EC-. The system had undergone disinfection with chlorine solution prior to repeat samples being collected. The August monthly sample was also collected on 8/29/2023 and resulted as TC-/EC-. |
10-25-2023
|
10-26-2023
|