ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0410606

Federal Type:

NC

Water System Name:

SOLDIER CAMP PERMITTEES

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A

Comments:

Activity Date:

06-01-1977





Parties Present
Name Organization Phone Number
PIHL, COLE ADEQ 602-771-4663
ROMANOV, JOSEPH R 520-235-3639


Deficiencies/Recommendations
Category Severity Description Code
Description Text
Comments Determine
Date
Resolved
Date
SO MIN 1 ->=1:500 Spring box does not have an air vent installed. 08-27-2018 03-21-2019
FW MIN 8 -Between 1:50,000 and 1:100,000 Storage tanks 001 (Main 1), 002 (Main 2) and 006 (Settling Tank) do not have #16 non-corrodible mesh screens installed on overflow pipes. 08-27-2018 10-26-2018
SO MIN 1 -1 Spring box does not have an air vent installed. 08-27-2018 03-21-2019
SO MIN 1 -1 Spring box does not have an air vent installed. 08-27-2018 03-21-2019
DS MIN The system has four Entry Point to Distribution System (EPDS) locations which do not have sample taps. 08-27-2018 10-29-2018
FW MIN Storage tanks 001 (Main 1), 002 (Main 2) and 005 (Fern Ridge) do not have #16 non-corrodible mesh screens installed on air vents. 08-27-2018 10-26-2018
FW MIN Spring box hatch is not properly sealed with a gasket. 08-27-2018 12-13-2018
SE SIG Spring box is not properly covered and locked to prevent access. Ladders to storage tanks 003 and 004 do not have proper security to prevent access to the tops of the tanks. The hatch to the ST006 (Settling Tank) is not properly covered and locked to prevent access. 08-27-2018 03-21-2019
FW MIN There is brush around the foundation of storage tank 005 (Fern Ridge). 08-27-2018 10-26-2018
FW MIN Storage tank 004 (Upper Soldier) has holes on top of the roof. 08-27-2018 10-26-2018