ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0402063

Federal Type:

NTNC

Water System Name:

COCHISE COUNTY COMMUNITY COLLEGE DISTRIC

Primary Source:

GW

Principal County Served:

COCHISE

System Status:

A - MAP

Comments:

Activity Date:

08-01-1963





Parties Present
Name Organization Phone Number
STRONG, CAMERON 254-405-2783


Deficiencies/Recommendations
Category Severity Description Code
Description Text
Comments Determine
Date
Resolved
Date
OT SIG routine samples were taken on 03/27/2023; results for both RTCR001 and RTCR002 were total coliform coliform positive/E coli negative (TC+/EC-). Residual chlorine readings were 0.18 and 0.04, respectively. (The RAA for RDL was 0.25 thought 03/31/2023) Repeat and triggered GWR samples were not taken within 24 hours of lab notification. They were taken on 04/06/2023. The residual chlorine readings were lower than the routine sample levels - 0.04, 0.02, 0.00 at the RTCR001 sites; all 0.00 at the RTCR002 sites. However, all results were total coliform and E. coli negative (TC- / EC-). Well #1 (55-601343) has been off-line since early March, undergoing repairs. Only Well #2 (55-601344) has been operating throughout this period. The chlorinator was not set to pump chlorine from that well into the tank, so the residual levels were lower than normal. 03-27-2023 04-06-2023