TR |
SIG |
|
Sept-Nov. 2017-PWS used backup storage tank while main storage tank taken out of service to
refurbish, and placed back in service on 11/10/17. PWS used chlorine treatment from Oct. 2017-
Jan.15, 2018. Coliform monitoring reported negative during this period. Last chlorine treatment on
1/15.18. Sample collected on 2/7/18, positive for coliform, no e.coli. Repeats collected within 24
hours of lab notice, all samples and raw sample were positive for coliform, no e.coli. Public notice
sent to residents and started chlorination treatment. 3/1/18-Assessment 2 completed-potential
source issue aging of well casing, March 2018, distribution samples negative, raw sample at well
head postive, no e.coli. PWS to continue chlorination until available finances for new well. |
03-02-2018
|
12-17-2019
|