Water System Detail Information

Water System No.:

AZ0410260

Federal Type:

C

Water System Name:

DOME WELL COOP

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

06-01-1989





Parties Present
Name Organization Phone Number
GOMEZ, RENE PDEQ 520-724-7365
MCCAIN, LUCAS R 520-261-4516


Deficiencies/Recommendations
Category Severity Description Code
Description Text
Comments Determine
Date
Resolved
Date
FW MIN 8 -Between 1:50,000 and 1:100,000 Deficiency #4: Overflow pipe is not screened. Technical Basis: Per Engineering Bulletin No.10, Chapter 6, E.6 OVERFLOW The overflow of an above ground storage unit shall open downward and be screened with 16-mesh non-corrodible screen installed within the pipe at a location least susceptible to damage by vandalism. 08-22-2023 01-29-2024
SM MIN 15 -15 Deficiency # 7: Emergency Operation Plan is not up-to-date. Technical Basis: Per Arizona Administrative Code R18-4-204. Emergency Operation Plan. The water supplier for a community water system shall develop and keep an emergency operation plan in an easily accessible location. 08-22-2023 09-11-2023
FW MIN Deficiency #6: Storage vent not installed. Technical Basis: Per Engineering Bulletin No.10, Chapter 6, E.9 VENTS Finished water storage units shall be vented. Vent shall be covered with 16-mesh non-corrodible screen installed within the pipe at a location least susceptible to damage by vandalism. 08-22-2023 12-28-2023
PU MIN Technical Basis: Per Engineering Bulletin No. 10, Chapter 3, A.2 PUMP INSTALLATION CONSIDERATIONS Pumps must be mounted on a solid concrete foundation. The pump base, pump and driving unit should be level and aligned. 08-22-2023 01-29-2024
FW MIN Deficiency #2: Storage tank drain valve not installed. Technical Basis: Per Engineering Bulletin No. 10, Chapter 6, E.4 DRAINS All finished water storage units have to be taken out of service for maintenance at periodic intervals for cleaning, repair or maintenance. Provisions shall be made in the design to permit complete isolation and drainage of each storage unit while maintaining service to the system. 08-22-2023 01-29-2024
FW REC Deficiency #3: Storage tank bedding requires minor repairs. Technical Basis: Per Engineering Bulletin No. 10, Chapter 6, E.5 FOUNDATION All storage units shall have adequate bedding or foundation commensurate with the soil bearing properties. 08-22-2023 01-29-2024