Deficiencies/Recommendations |
Category |
Severity |
Description Code Description Text |
Comments |
Determine Date |
Resolved Date |
FW |
MIN |
8 -Between 1:50,000 and 1:100,000
|
The storage tank's overflow pipe's screen is too big (not a #16 non-corrodible mesh). |
09-14-2017
|
10-17-2017
|
SO |
REC |
9 -<1:100,000
|
The raw water sample tap and the sample tap at the EPDS have threads. |
09-14-2017
|
|
FW |
REC |
102 -Facility Center/Centroid
|
Some dirt is accumulating at the base of the storage tank but the area around the tank is graded to provide drainage away from tank. There is also a lot of dirt accumulating where the storage tank's outlet and inlet are located. |
09-14-2017
|
|
SE |
MIN |
|
The storage tank is not enclosed by a building or security fencing. |
09-14-2017
|
10-11-2017
|
FW |
MIN |
|
The storage tank's hatch does not have a gasket/seal. |
09-14-2017
|
11-07-2017
|