ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411031

Federal Type:

C

Water System Name:

KEARNY TOWN OF

Primary Source:

GW

Principal County Served:

PINAL

System Status:

A - MAP

Comments:

Activity Date:

1958-01-01



Analyte
Code
Analyte
Name
Sample
Type
Sample
No.
Date Sample
Point
Sample
Result
Sample
UOM
Sample
Less Than
Indicator
Detection Limit MCL Laboratory
1005 ARSENIC RT 380-81375-3 2024-02-01 EPDS003 6.0 UG/L .01 MG/L EUROFINS DRINKING WATER TESTING CA
1005 ARSENIC RT 380-49187-1 2023-05-30 EPDS001 6.5 UG/L .01 MG/L EUROFINS DRINKING WATER TESTING CA
1005 ARSENIC RT 202004280027I 2020-04-27 EPDS001 6 UG/L .01 MG/L EUROFINS EATON ANALYTICAL INC
1005 ARSENIC RT 201105170173I 2011-05-16 EPDS001 .0056 MG/L .01 MG/L MWH LABS INC
1005 ARSENIC RT 201105170174I 2011-05-16 EPDS002 .0056 MG/L .01 MG/L MWH LABS INC
1005 ARSENIC RT 2802260015I 2008-02-25 EPDS002 .001 MG/L .01 MG/L MWH LABS INC
1005 ARSENIC RT 07120193-01A 2007-12-06 EPDS002 .0047 MG/L .01 MG/L TRANSWEST GEOCHEM INC PHOENIX
1005 ARSENIC RT 0703795-02A 2007-03-30 EPDS002 .0039 MG/L .01 MG/L TRANSWEST GEOCHEM INC PHOENIX
1005 ARSENIC RT 2506140003I 2005-06-13 EPDS001 .0052 MG/L .01 MG/L MWH LABS INC
1005 ARSENIC RT 2506140004I 2005-06-13 EPDS002 MG/L < 0 MG/L .01 MG/L MWH LABS INC
1005 ARSENIC RT 051702-28I 2002-05-16 EPDS001 .0052 MG/L .01 MG/L AQUA TECH ENVIRONMENTAL LABORATORIES
1005 ARSENIC RT 051702-29I 2002-05-16 EPDS002 null < .003 MG/L .01 MG/L AQUA TECH ENVIRONMENTAL LABORATORIES
1005 ARSENIC RT 2001040141I 1999-12-23 EPDS001 .0047 MG/L .01 MG/L MWH LABS INC
1005 ARSENIC RT 2001040142I 1999-12-23 EPDS002 .012 MG/L .01 MG/L MWH LABS INC
1005 ARSENIC RT BB-05895 1996-10-01 EPDS002 null < .005 MG/L .01 MG/L AQUATIC CONSULTING TESTING
1005 ARSENIC RT BB-05896 1996-10-01 EPDS001 null < .005 MG/L .01 MG/L AQUATIC CONSULTING TESTING
1005 ARSENIC RT BB-02499-I 1996-04-26 EPDS001 null < .005 MG/L .01 MG/L AQUATIC CONSULTING TESTING
1005 ARSENIC RT L93-0872 1993-05-19 EPDS001 null < .005 MG/L .01 MG/L AQUATIC CONSULTING TESTING
1005 ARSENIC RT L93-0873 1993-05-19 EPDS002 .016 MG/L .01 MG/L AQUATIC CONSULTING TESTING
1005 ARSENIC RT L93-0874 1993-05-19 EPDS002 null < .005 MG/L .01 MG/L AQUATIC CONSULTING TESTING