ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407025

Federal Type:

C

Water System Name:

PHOENIX CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
2002026452 1074 ANTIMONY, TOTAL 2002-05-30 EPDS293 < MRL 0.001 MG/L .006 MG/L 2002-01-01
2004-12-31
2002026452 1005 ARSENIC 2002-05-30 EPDS293 .0132  MG/L .01 MG/L 2002-01-01
2004-12-31
2002026452 1010 BARIUM 2002-05-30 EPDS293 .0062  MG/L 2 MG/L 2002-01-01
2004-12-31
2002026452 1075 BERYLLIUM, TOTAL 2002-05-30 EPDS293 < MRL 0.001 MG/L .004 MG/L 2002-01-01
2004-12-31
2002026452 1015 CADMIUM 2002-05-30 EPDS293 < MRL 0.001 MG/L .005 MG/L 2002-01-01
2004-12-31
2002026452 1020 CHROMIUM 2002-05-30 EPDS293 .0138  MG/L .1 MG/L 2002-01-01
2004-12-31
2002026452 1025 FLUORIDE 2002-05-30 EPDS293 .61  MG/L 4 MG/L 2002-01-01
2004-12-31
2002026452 1036 NICKEL 2002-05-30 EPDS293 < MRL 0.001 MG/L 2002-01-01
2004-12-31
2002026452 1045 SELENIUM 2002-05-30 EPDS293 < MRL 0.001 MG/L .05 MG/L 2002-01-01
2004-12-31
2002026452 1052 SODIUM 2002-05-30 EPDS293 32  MG/L 3000 MG/L 2002-01-01
2004-12-31
2002026452 1085 THALLIUM, TOTAL 2002-05-30 EPDS293 < MRL 0.001 MG/L .002 MG/L 2002-01-01
2004-12-31