ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407025

Federal Type:

C

Water System Name:

PHOENIX CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
2014009692 1074 ANTIMONY, TOTAL 2014-02-26 EPDS290 < MRL 0.001 MG/L .006 MG/L 2014-01-01
2016-12-31
2014009692 1005 ARSENIC 2014-02-26 EPDS290 .004  MG/L .01 MG/L 2014-01-01
2016-12-31
2014009692 1010 BARIUM 2014-02-26 EPDS290 < MRL 0.01 MG/L 2 MG/L 2014-01-01
2016-12-31
2014009692 1075 BERYLLIUM, TOTAL 2014-02-26 EPDS290 < MRL 0.001 MG/L .004 MG/L 2014-01-01
2016-12-31
2014009692 1015 CADMIUM 2014-02-26 EPDS290 < MRL 0.002 MG/L .005 MG/L 2014-01-01
2016-12-31
2014009692 1020 CHROMIUM 2014-02-26 EPDS290 .006  MG/L .1 MG/L 2014-01-01
2016-12-31
2014009692 1035 MERCURY 2014-02-26 EPDS290 < MRL 0.0002 MG/L .002 MG/L 2014-01-01
2016-12-31
2014009692 1036 NICKEL 2014-02-26 EPDS290 < MRL 0.02 MG/L 2014-01-01
2016-12-31
2014009692 1045 SELENIUM 2014-02-26 EPDS290 < MRL 0.001 MG/L .05 MG/L 2014-01-01
2016-12-31
2014009692 1052 SODIUM 2014-02-26 EPDS290 29.8  MG/L 3000 MG/L 2014-01-01
2016-12-31
2014009692 1085 THALLIUM, TOTAL 2014-02-26 EPDS290 < MRL 0.001 MG/L .002 MG/L 2014-01-01
2016-12-31