ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407025

Federal Type:

C

Water System Name:

PHOENIX CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
70003212 1010 BARIUM 1997-02-11 EPDS113 .02  MG/L 2 MG/L
70003212 1017 CHLORIDE 1997-02-11 EPDS113 35  MG/L 250 MG/L
70003212 1022 COPPER, FREE 1997-02-11 EPDS113 .04  MG/L 1.3 MG/L
70003212 1025 FLUORIDE 1997-02-11 EPDS113 .43  MG/L 4 MG/L
70003212 1028 IRON 1997-02-11 EPDS113 < MRL 0.01 MG/L .3 MG/L
70003212 1032 MANGANESE 1997-02-11 EPDS113 < MRL 0.003 MG/L .05 MG/L
70003212 1035 MERCURY 1997-02-11 EPDS113 < MRL 0.0002 MG/L .002 MG/L
70003212 1040 NITRATE 1997-02-11 EPDS113 1.5  MG/L 10 MG/L
70003212 1041 NITRITE 1997-02-11 EPDS113 < MRL 0.1 MG/L 1 MG/L
70003212 1052 SODIUM 1997-02-11 EPDS113 46  MG/L 3000 MG/L
70003212 1055 SULFATE 1997-02-11 EPDS113 86  MG/L 250 MG/L
70003212 1095 ZINC 1997-02-11 EPDS113 < MRL 0.01 MG/L 5 MG/L