ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407025

Federal Type:

C

Water System Name:

PHOENIX CITY OF

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
980005572 1074 ANTIMONY, TOTAL 1998-06-10 EPDS113 < MRL 0.003 MG/L .006 MG/L
980005572 1005 ARSENIC 1998-06-10 EPDS113 .011  MG/L .01 MG/L
980005572 1010 BARIUM 1998-06-10 EPDS113 < MRL 0.05 MG/L 2 MG/L
980005572 1075 BERYLLIUM, TOTAL 1998-06-10 EPDS113 < MRL 0.0005 MG/L .004 MG/L
980005572 1015 CADMIUM 1998-06-10 EPDS113 < MRL 0.0005 MG/L .005 MG/L
980005572 1020 CHROMIUM 1998-06-10 EPDS113 < MRL 0.005 MG/L .1 MG/L
980005572 1025 FLUORIDE 1998-06-10 EPDS113 .5  MG/L 4 MG/L
980005572 1035 MERCURY 1998-06-10 EPDS113 < MRL 0.0002 MG/L .002 MG/L
980005572 1036 NICKEL 1998-06-10 EPDS113 < MRL 0.005 MG/L
980005572 1040 NITRATE 1998-06-10 EPDS113 1.1  MG/L 10 MG/L
980005572 1041 NITRITE 1998-06-10 EPDS113 < MRL 0.1 MG/L 1 MG/L
980005572 1045 SELENIUM 1998-06-10 EPDS113 < MRL 0.01 MG/L .05 MG/L
980005572 1052 SODIUM 1998-06-10 EPDS113 40.4  MG/L 3000 MG/L
980005572 1055 SULFATE 1998-06-10 EPDS113 44  MG/L 250 MG/L