ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0407017

Federal Type:

C

Water System Name:

EPCOR - CHAPARRAL CITY

Primary Source:

SW

Principal County Served:

MARICOPA

System Status:

A

Comments:

Activity Date:

1989-11-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
PQA0604-01 1074 ANTIMONY, TOTAL 2007-01-22 EPDS005 < MRL 0.002 MG/L .006 MG/L 2007-01-01
2007-12-31
PQA0604-01 1005 ARSENIC 2007-01-22 EPDS005 0.0011  MG/L .01 MG/L 2007-01-01
2007-12-31
PQA0604-01 1010 BARIUM 2007-01-22 EPDS005 0.14  MG/L 2 MG/L 2007-01-01
2007-12-31
PQA0604-01 1075 BERYLLIUM, TOTAL 2007-01-22 EPDS005 < MRL 0.004 MG/L .004 MG/L 2007-01-01
2007-12-31
PQA0604-01 1015 CADMIUM 2007-01-22 EPDS005 0.0054  MG/L .005 MG/L 2007-01-01
2007-12-31
PQA0604-01 1020 CHROMIUM 2007-01-22 EPDS005 < MRL 0.01 MG/L .1 MG/L 2007-01-01
2007-12-31
PQA0604-01 1025 FLUORIDE 2007-01-22 EPDS005 0.32  MG/L 4 MG/L 2007-01-01
2007-12-31
PQA0604-01 1035 MERCURY 2007-01-22 EPDS005 < MRL 0.0002 MG/L .002 MG/L 2007-01-01
2007-12-31
PQA0604-01 1036 NICKEL 2007-01-22 EPDS005 < MRL 0.05 MG/L 2007-01-01
2007-12-31
PQA0604-01 1045 SELENIUM 2007-01-22 EPDS005 < MRL 0.002 MFL .05 MG/L 2007-01-01
2007-12-31
PQA0604-01 1052 SODIUM 2007-01-22 EPDS005 97  MG/L 3000 MG/L 2007-01-01
2007-12-31
PQA0604-01 1085 THALLIUM, TOTAL 2007-01-22 EPDS005 < MRL 0.001 MG/L .002 MG/L 2007-01-01
2007-12-31