ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0405005

Federal Type:

C

Water System Name:

SAFFORD CITY OF

Primary Source:

GW

Principal County Served:

GRAHAM

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
550-157232-1 1074 ANTIMONY, TOTAL 2021-01-25 EPDS012 < MRL 0.001 MG/L .006 MG/L 2021-01-01
2023-12-31
550-157232-1 1005 ARSENIC 2021-01-25 EPDS012 0.0012  MG/L .01 MG/L 2021-01-01
2023-12-31
550-157232-1 1010 BARIUM 2021-01-25 EPDS012 0.0059  MG/L 2 MG/L 2021-01-01
2023-12-31
550-157232-1 1075 BERYLLIUM, TOTAL 2021-01-25 EPDS012 < MRL 0.0004 MG/L .004 MG/L 2021-01-01
2023-12-31
550-157232-1 1015 CADMIUM 2021-01-25 EPDS012 < MRL 0.0001 MG/L .005 MG/L 2021-01-01
2023-12-31
550-157232-1 1020 CHROMIUM 2021-01-25 EPDS012 < MRL 0.001 MG/L .1 MG/L 2021-01-01
2023-12-31
550-157232-1 1024 CYANIDE 2021-01-25 EPDS012 < MRL 0.05 MG/L .2 MG/L 2021-01-01
2023-12-31
550-157232-1 1035 MERCURY 2021-01-25 EPDS012 < MRL 0.0002 MG/L .002 MG/L 2021-01-01
2023-12-31
550-157232-1 1036 NICKEL 2021-01-25 EPDS012 < MRL 0.002 MG/L 2021-01-01
2023-12-31
550-157232-1 1052 SODIUM 2021-01-25 EPDS012 110  MG/L 3000 MG/L 2021-01-01
2023-12-31
550-157232-1 1085 THALLIUM, TOTAL 2021-01-25 EPDS012 0.00010  MG/L .002 MG/L 2021-01-01
2023-12-31