ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0410010

Federal Type:

NTNC

Water System Name:

MARANA TANGERINE BUSINESS PARK

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A - MAP

Comments:

Activity Date:

2018-05-08



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
201903220029I 1074 ANTIMONY, TOTAL 2019-03-21 EPDS001 < MRL 0.001 MG/L .006 MG/L 2019-01-01
2021-12-31
201903220029I 1005 ARSENIC 2019-03-21 EPDS001 0.0022  MG/L .01 MG/L 2019-01-01
2021-12-31
201903220029I 1010 BARIUM 2019-03-21 EPDS001 0.074  MG/L 2 MG/L 2019-01-01
2021-12-31
201903220029I 1075 BERYLLIUM, TOTAL 2019-03-21 EPDS001 < MRL 0.001 MG/L .004 MG/L 2019-01-01
2021-12-31
201903220029I 1015 CADMIUM 2019-03-21 EPDS001 < MRL 0.0005 MG/L .005 MG/L 2019-01-01
2021-12-31
201903220029I 1020 CHROMIUM 2019-03-21 EPDS001 < MRL 0.001 MG/L .1 MG/L 2019-01-01
2021-12-31
201903220029I 1024 CYANIDE 2019-03-21 EPDS001 < MRL 0.025 MG/L .2 MG/L 2019-01-01
2021-12-31
201903220029I 1035 MERCURY 2019-03-21 EPDS001 < MRL 0.0002 MG/L .002 MG/L 2019-01-01
2021-12-31
201903220029I 1036 NICKEL 2019-03-21 EPDS001 < MRL 0.005 MG/L 2019-01-01
2021-12-31
201903220029I 1040 NITRATE 2019-03-21 EPDS001 1.7  MG/L 10 MG/L 2019-01-01
2019-12-31
201903220029I 1038 NITRATE-NITRITE 2019-03-21 EPDS001 1.7  MG/L 10 MG/L
201903220029I 1041 NITRITE 2019-03-21 EPDS001 < MRL 0.05 MG/L 1 MG/L 2019-01-01
2027-12-31
201903220029I 1045 SELENIUM 2019-03-21 EPDS001 < MRL 0.005 MG/L .05 MG/L 2019-01-01
2021-12-31
201903220029I 1085 THALLIUM, TOTAL 2019-03-21 EPDS001 < MDL 0.001 MG/L .002 MG/L 2019-01-01
2021-12-31