ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0411409

Federal Type:

C

Water System Name:

VALLE ESCONDIDO

Primary Source:

GW

Principal County Served:

PINAL

System Status:

A - MAP

Comments:

Activity Date:

2012-08-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
202004300055I 1074 ANTIMONY, TOTAL 2020-04-29 EPDS001 < MRL 1 UG/L .006 MG/L 2020-01-01
2022-12-31
202004300055I 1005 ARSENIC 2020-04-29 EPDS001 6.1  UG/L .01 MG/L 2020-04-01
2020-06-30
202004300055I 1010 BARIUM 2020-04-29 EPDS001 6.4  UG/L 2 MG/L 2020-01-01
2022-12-31
202004300055I 1075 BERYLLIUM, TOTAL 2020-04-29 EPDS001 < MRL 1 UG/L .004 MG/L 2020-01-01
2022-12-31
202004300055I 1015 CADMIUM 2020-04-29 EPDS001 < MRL 0.5 UG/L .005 MG/L 2020-01-01
2022-12-31
202004300055I 1020 CHROMIUM 2020-04-29 EPDS001 20  UG/L .1 MG/L 2020-01-01
2022-12-31
202004300055I 1024 CYANIDE 2020-04-29 EPDS001 < MRL 0.025 MG/L .2 MG/L 2020-01-01
2022-12-31
202004300055I 1025 FLUORIDE 2020-04-29 EPDS001 1.8  MG/L 4 MG/L 2020-01-01
2022-12-31
202004300055I 1035 MERCURY 2020-04-29 EPDS001 < MRL 0.2 UG/L .002 MG/L 2020-01-01
2022-12-31
202004300055I 1036 NICKEL 2020-04-29 EPDS001 < MRL 5 UG/L 2020-01-01
2022-12-31
202004300055I 1040 NITRATE 2020-04-29 EPDS001 4.2  MG/L 10 MG/L 2020-01-01
2020-12-31
202004300055I 1045 SELENIUM 2020-04-29 EPDS001 < MRL 5 UG/L .05 MG/L 2020-01-01
2022-12-31
202004300055I 1052 SODIUM 2020-04-29 EPDS001 190  MG/L 3000 MG/L 2020-01-01
2022-12-31
202004300055I 1085 THALLIUM, TOTAL 2020-04-29 EPDS001 < MRL 1 UG/L .002 MG/L 2020-01-01
2022-12-31