ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0404319

Federal Type:

NC

Water System Name:

CAMP GERONIMO

Primary Source:

GW

Principal County Served:

GILA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
CB02944 1074 ANTIMONY, TOTAL 2019-04-02 EPDS003 < MRL 0.001 MG/L .006 MG/L
CB02944 1005 ARSENIC 2019-04-02 EPDS003 < MDL 0.005 MG/L .01 MG/L
CB02944 1010 BARIUM 2019-04-02 EPDS003 0.19  MG/L 2 MG/L
CB02944 1075 BERYLLIUM, TOTAL 2019-04-02 EPDS003 < MRL 0.001 MG/L .004 MG/L
CB02944 1015 CADMIUM 2019-04-02 EPDS003 < MRL 0.001 MG/L .005 MG/L
CB02944 1020 CHROMIUM 2019-04-02 EPDS003 < MRL 0.005 MG/L .1 MG/L
CB02944 1024 CYANIDE 2019-04-02 EPDS003 < MRL 0.01 MG/L .2 MG/L
CB02944 1025 FLUORIDE 2019-04-02 EPDS003 < MDL 0.5 MG/L 4 MG/L
CB02944 1035 MERCURY 2019-04-02 EPDS003 < MRL 0.00005 MG/L .002 MG/L
CB02944 1036 NICKEL 2019-04-02 EPDS003 0.0031  MG/L
CB02944 1040 NITRATE 2019-04-02 EPDS003 0.14  MG/L 10 MG/L 2019-01-01
2019-12-31
CB02944 1038 NITRATE-NITRITE 2019-04-02 EPDS003 0.14  MG/L 10 MG/L
CB02944 1041 NITRITE 2019-04-02 EPDS003 < MRL 0.01 MG/L 1 MG/L 2017-01-01
2025-12-31
CB02944 1045 SELENIUM 2019-04-02 EPDS003 < MRL 0.002 MG/L .05 MG/L
CB02944 1085 THALLIUM, TOTAL 2019-04-02 EPDS003 < MDL 0.001 MG/L .002 MG/L