ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0404032

Federal Type:

C

Water System Name:

PAYSON TOWN OF

Primary Source:

SW

Principal County Served:

GILA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
380-54465-3I 1074 ANTIMONY, TOTAL 2023-07-11 EPDS023 < MRL 0.001 MG/L .006 MG/L 2023-01-01
2023-12-31
380-54465-3I 1005 ARSENIC 2023-07-11 EPDS023 < MRL 0.001 MG/L .01 MG/L 2023-01-01
2023-12-31
380-54465-3I 1010 BARIUM 2023-07-11 EPDS023 0.068  MG/L 2 MG/L 2023-01-01
2023-12-31
380-54465-3I 1075 BERYLLIUM, TOTAL 2023-07-11 EPDS023 < MRL 0.001 MG/L .004 MG/L 2023-01-01
2023-12-31
380-54465-3I 1015 CADMIUM 2023-07-11 EPDS023 < MRL 0.0005 MG/L .005 MG/L 2023-01-01
2023-12-31
380-54465-3I 1020 CHROMIUM 2023-07-11 EPDS023 < MRL 0.001 MG/L .1 MG/L 2023-01-01
2023-12-31
380-54465-3I 1024 CYANIDE 2023-07-11 EPDS023 < MRL 0.025 MG/L .2 MG/L 2023-01-01
2023-12-31
380-54465-3I 1025 FLUORIDE 2023-07-11 EPDS023 0.46  MG/L 4 MG/L 2023-01-01
2023-12-31
380-54465-3I 1035 MERCURY 2023-07-11 EPDS023 0.00076  MG/L .002 MG/L 2023-01-01
2023-12-31
380-54465-3I 1036 NICKEL 2023-07-11 EPDS023 < MRL 0.005 MG/L 2023-01-01
2023-12-31
380-54465-3I 1040 NITRATE 2023-07-11 EPDS023 1.8  MG/L 10 MG/L 2023-01-01
2023-12-31
380-54465-3I 1045 SELENIUM 2023-07-11 EPDS023 < MRL 0.005 MG/L .05 MG/L 2023-01-01
2023-12-31
380-54465-3I 1052 SODIUM 2023-07-11 EPDS023 19  MG/L 3000 MG/L 2023-01-01
2023-12-31
380-54465-3I 1085 THALLIUM, TOTAL 2023-07-11 EPDS023 < MDL 0.001 MG/L .002 MG/L 2023-01-01
2023-12-31