ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0404032

Federal Type:

C

Water System Name:

PAYSON TOWN OF

Primary Source:

SW

Principal County Served:

GILA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
202009160534I 1074 ANTIMONY, TOTAL 2020-09-15 EPDS018 < MRL 0.001 MG/L .006 MG/L 2020-01-01
2020-12-31
202009160534I 1005 ARSENIC 2020-09-15 EPDS018 < MRL 0.001 MG/L .01 MG/L 2020-01-01
2020-12-31
202009160534I 1010 BARIUM 2020-09-15 EPDS018 0.040  MG/L 2 MG/L 2020-01-01
2020-12-31
202009160534I 1075 BERYLLIUM, TOTAL 2020-09-15 EPDS018 < MRL 0.001 MG/L .004 MG/L 2020-01-01
2020-12-31
202009160534I 1015 CADMIUM 2020-09-15 EPDS018 < MRL 0.0005 MG/L .005 MG/L 2020-01-01
2020-12-31
202009160534I 1020 CHROMIUM 2020-09-15 EPDS018 < MRL 0.001 MG/L .1 MG/L 2020-01-01
2020-12-31
202009160534I 1024 CYANIDE 2020-09-15 EPDS018 < MRL 0.025 MG/L .2 MG/L 2020-01-01
2020-12-31
202009160534I 1025 FLUORIDE 2020-09-15 EPDS018 0.65  MG/L 4 MG/L 2020-01-01
2020-12-31
202009160534I 1035 MERCURY 2020-09-15 EPDS018 < MRL 0.0002 MG/L .002 MG/L 2020-01-01
2020-12-31
202009160534I 1036 NICKEL 2020-09-15 EPDS018 < MRL 0.005 MG/L 2020-01-01
2020-12-31
202009160534I 1045 SELENIUM 2020-09-15 EPDS018 < MRL 0.005 MG/L .05 MG/L 2020-01-01
2020-12-31
202009160534I 1052 SODIUM 2020-09-15 EPDS018 18  MG/L 3000 MG/L 2020-01-01
2020-12-31
202009160534I 1085 THALLIUM, TOTAL 2020-09-15 EPDS018 < MDL 0.001 MG/L .002 MG/L 2020-01-01
2020-12-31