ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0403026

Federal Type:

C

Water System Name:

WILLIAMS CITY OF

Primary Source:

SW

Principal County Served:

COCONINO

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
201705170129I 1074 ANTIMONY, TOTAL 2017-05-16 EPDS001 < MRL 1 UG/L .006 MG/L 2017-01-01
2019-12-31
201705170129I 1005 ARSENIC 2017-05-16 EPDS001 1.4  UG/L .01 MG/L 2017-01-01
2019-12-31
201705170129I 1010 BARIUM 2017-05-16 EPDS001 280.000  UG/L 2 MG/L 2017-01-01
2019-12-31
201705170129I 1075 BERYLLIUM, TOTAL 2017-05-16 EPDS001 < MRL 1 UG/L .004 MG/L 2017-01-01
2019-12-31
201705170129I 1015 CADMIUM 2017-05-16 EPDS001 < MRL 0.5 UG/L .005 MG/L 2017-01-01
2019-12-31
201705170129I 1020 CHROMIUM 2017-05-16 EPDS001 2.3  UG/L .1 MG/L 2017-01-01
2019-12-31
201705170129I 1024 CYANIDE 2017-05-16 EPDS001 < MRL 0.025 MG/L .2 MG/L 2017-01-01
2019-12-31
201705170129I 1025 FLUORIDE 2017-05-16 EPDS001 0.098  MG/L 4 MG/L 2017-01-01
2019-12-31
201705170129I 1035 MERCURY 2017-05-16 EPDS001 < MRL 0.2 UG/L .002 MG/L 2017-01-01
2019-12-31
201705170129I 1036 NICKEL 2017-05-16 EPDS001 < MRL 5 UG/L 2017-01-01
2019-12-31
201705170129I 1040 NITRATE 2017-05-16 EPDS001 0.25  MG/L 10 MG/L 2017-01-01
2017-12-31
201705170129I 1045 SELENIUM 2017-05-16 EPDS001 < MRL 5 UG/L .05 MG/L 2017-01-01
2019-12-31
201705170129I 1052 SODIUM 2017-05-16 EPDS001 6.2  MG/L 3000 MG/L 2017-01-01
2019-12-31
201705170129I 1085 THALLIUM, TOTAL 2017-05-16 EPDS001 < MRL 1 UG/L .002 MG/L 2017-01-01
2019-12-31