ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0403018

Federal Type:

C

Water System Name:

PONDEROSA UTILITY CORP

Primary Source:

GW

Principal County Served:

COCONINO

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
201604140039I 1074 ANTIMONY, TOTAL 2016-04-13 EPDS002 < MRL 0.001 MG/L .006 MG/L 2016-01-01
2018-12-31
201604140039I 1005 ARSENIC 2016-04-13 EPDS002 .0026  MG/L .01 MG/L 2016-01-01
2018-12-31
201604140039I 1010 BARIUM 2016-04-13 EPDS002 .039  MG/L 2 MG/L 2016-01-01
2018-12-31
201604140039I 1075 BERYLLIUM, TOTAL 2016-04-13 EPDS002 < MRL 0.001 MG/L .004 MG/L 2016-01-01
2018-12-31
201604140039I 1015 CADMIUM 2016-04-13 EPDS002 < MRL 0.0005 MG/L .005 MG/L 2016-01-01
2018-12-31
201604140039I 1020 CHROMIUM 2016-04-13 EPDS002 < MRL 0.001 MG/L .1 MG/L 2016-01-01
2018-12-31
201604140039I 1024 CYANIDE 2016-04-13 EPDS002 < MRL 0.025 MG/L .2 MG/L 2016-01-01
2018-12-31
201604140039I 1025 FLUORIDE 2016-04-13 EPDS002 .082  MG/L 4 MG/L 2016-01-01
2018-12-31
201604140039I 1035 MERCURY 2016-04-13 EPDS002 < MRL 0.0002 MG/L .002 MG/L 2016-01-01
2018-12-31
201604140039I 1036 NICKEL 2016-04-13 EPDS002 < MRL 0.005 MG/L 2016-01-01
2018-12-31
201604140039I 1040 NITRATE 2016-04-13 EPDS002 .15  MG/L 10 MG/L 2016-01-01
2016-12-31
201604140039I 1045 SELENIUM 2016-04-13 EPDS002 < MRL 0.005 MG/L .05 MG/L 2016-01-01
2018-12-31
201604140039I 1052 SODIUM 2016-04-13 EPDS002 3.6  MG/L 3000 MG/L 2016-01-01
2018-12-31
201604140039I 1085 THALLIUM, TOTAL 2016-04-13 EPDS002 < MDL 0.001 MG/L .002 MG/L 2016-01-01
2018-12-31