ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0420557

Federal Type:

C

Water System Name:

ADOC TUCSON

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
032905-22I 1074 ANTIMONY, TOTAL 2005-03-29 EPDS001 < MDL 0 MG/L .006 MG/L 2003-01-01
2005-12-31
032905-22I 1005 ARSENIC 2005-03-29 EPDS001 .004  MG/L .01 MG/L 2003-01-01
2005-12-31
032905-22I 1010 BARIUM 2005-03-29 EPDS001 .044  MG/L 2 MG/L 2003-01-01
2005-12-31
032905-22I 1075 BERYLLIUM, TOTAL 2005-03-29 EPDS001 < MDL 0 MG/L .004 MG/L 2003-01-01
2005-12-31
032905-22I 1015 CADMIUM 2005-03-29 EPDS001 < MDL 0 MG/L .005 MG/L 2003-01-01
2005-12-31
032905-22I 1020 CHROMIUM 2005-03-29 EPDS001 < MDL 0 MG/L .1 MG/L 2003-01-01
2005-12-31
032905-22I 1024 CYANIDE 2005-03-29 EPDS001 < MDL 0 MG/L .2 MG/L 2003-01-01
2005-12-31
032905-22I 1025 FLUORIDE 2005-03-29 EPDS001 .29  MG/L 4 MG/L 2003-01-01
2005-12-31
032905-22I 1035 MERCURY 2005-03-29 EPDS001 < MDL 0 MG/L .002 MG/L 2003-01-01
2005-12-31
032905-22I 1036 NICKEL 2005-03-29 EPDS001 < MDL 0 MG/L 2003-01-01
2005-12-31
032905-22I 1045 SELENIUM 2005-03-29 EPDS001 < MDL 0 MG/L .05 MG/L 2003-01-01
2005-12-31
032905-22I 1085 THALLIUM, TOTAL 2005-03-29 EPDS001 < MDL 0 MG/L .002 MG/L 2003-01-01
2005-12-31