ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0420549

Federal Type:

C

Water System Name:

USAF DAVIS MONTHAN AFB

Primary Source:

GW

Principal County Served:

PIMA

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
955664 1074 ANTIMONY, TOTAL 2003-10-14 EPDS006 < MRL 0.001 MG/L .006 MG/L 2003-01-01
2005-12-31
955664 1005 ARSENIC 2003-10-14 EPDS006 .0029  MG/L .01 MG/L 2003-01-01
2005-12-31
955664 1010 BARIUM 2003-10-14 EPDS006 .033  MG/L 2 MG/L 2003-01-01
2005-12-31
955664 1075 BERYLLIUM, TOTAL 2003-10-14 EPDS006 < MRL 0.0003 MG/L .004 MG/L 2003-01-01
2005-12-31
955664 1015 CADMIUM 2003-10-14 EPDS006 < MRL 0.001 MG/L .005 MG/L 2003-01-01
2005-12-31
955664 1020 CHROMIUM 2003-10-14 EPDS006 .0091  MG/L .1 MG/L 2003-01-01
2005-12-31
955664 1024 CYANIDE 2003-10-14 EPDS006 < MRL 0.02 MG/L .2 MG/L 2003-01-01
2005-12-31
955664 1035 MERCURY 2003-10-14 EPDS006 < MRL 0.0001 MG/L .002 MG/L 2003-01-01
2005-12-31
955664 1036 NICKEL 2003-10-14 EPDS006 .002  MG/L 2003-01-01
2005-12-31
955664 1045 SELENIUM 2003-10-14 EPDS006 < MRL 0.002 MG/L .05 MG/L 2003-01-01
2005-12-31
955664 1052 SODIUM 2003-10-14 EPDS006 24  MG/L 3000 MG/L 2003-01-01
2005-12-31
955664 1085 THALLIUM, TOTAL 2003-10-14 EPDS006 < MRL 0.0004 MG/L .002 MG/L 2003-01-01
2005-12-31