ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0403008

Federal Type:

C

Water System Name:

FLAGSTAFF CITY OF

Primary Source:

SW

Principal County Served:

COCONINO

System Status:

A

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
202205260918I 1074 ANTIMONY, TOTAL 2022-05-25 EPDS010 < MRL 0.001 MG/L .006 MG/L 2021-01-01
2023-12-31
202205260918I 1005 ARSENIC 2022-05-25 EPDS010 0.0082  MG/L .01 MG/L 2021-01-01
2023-12-31
202205260918I 1010 BARIUM 2022-05-25 EPDS010 0.18  MG/L 2 MG/L 2021-01-01
2023-12-31
202205260918I 1075 BERYLLIUM, TOTAL 2022-05-25 EPDS010 < MRL 0.001 MG/L .004 MG/L 2021-01-01
2023-12-31
202205260918I 1015 CADMIUM 2022-05-25 EPDS010 < MRL 0.0005 MG/L .005 MG/L 2021-01-01
2023-12-31
202205260918I 1020 CHROMIUM 2022-05-25 EPDS010 < MRL 0.001 MG/L .1 MG/L 2021-01-01
2023-12-31
202205260918I 1024 CYANIDE 2022-05-25 EPDS010 < MRL 0.005 MG/L .2 MG/L 2021-01-01
2023-12-31
202205260918I 1035 MERCURY 2022-05-25 EPDS010 < MRL 0.0002 MG/L .002 MG/L 2021-01-01
2023-12-31
202205260918I 1036 NICKEL 2022-05-25 EPDS010 < MRL 0.005 MG/L 2021-01-01
2023-12-31
202205260918I 1045 SELENIUM 2022-05-25 EPDS010 < MRL 0.005 MG/L .05 MG/L 2021-01-01
2023-12-31
202205260918I 1052 SODIUM 2022-05-25 EPDS010 8.2  MG/L 3000 MG/L 2021-01-01
2023-12-31
202205260918I 1085 THALLIUM, TOTAL 2022-05-25 EPDS010 < MRL 0.001 MG/L .002 MG/L 2021-01-01
2023-12-31