ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0403005

Federal Type:

C

Water System Name:

DONEY PARK WATER

Primary Source:

GW

Principal County Served:

COCONINO

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
0021719-01 1074 ANTIMONY, TOTAL 2010-02-23 EPDS008 < MRL 0.0005 MG/L .006 MG/L
0021719-01 1005 ARSENIC 2010-02-23 EPDS008 .0014  MG/L .01 MG/L
0021719-01 1010 BARIUM 2010-02-23 EPDS008 .91  MG/L 2 MG/L
0021719-01 1075 BERYLLIUM, TOTAL 2010-02-23 EPDS008 < MRL 0.002 MG/L .004 MG/L
0021719-01 1015 CADMIUM 2010-02-23 EPDS008 < MRL 0.0001 MG/L .005 MG/L
0021719-01 1020 CHROMIUM 2010-02-23 EPDS008 < MRL 0.005 MG/L .1 MG/L
0021719-01 1024 CYANIDE 2010-02-23 EPDS008 < MRL 0.01 MG/L .2 MG/L
0021719-01 1025 FLUORIDE 2010-02-23 EPDS008 < MRL 0.5 MG/L 4 MG/L
0021719-01 1035 MERCURY 2010-02-23 EPDS008 < MRL 0.0002 MG/L .002 MG/L
0021719-01 1036 NICKEL 2010-02-23 EPDS008 < MRL 0.02 MG/L
0021719-01 1045 SELENIUM 2010-02-23 EPDS008 .002  MG/L .05 MG/L
0021719-01 1052 SODIUM 2010-02-23 EPDS008 6  MG/L 3000 MG/L
0021719-01 1055 SULFATE 2010-02-23 EPDS008 < MRL 5 MG/L 250 MG/L
0021719-01 1085 THALLIUM, TOTAL 2010-02-23 EPDS008 < MRL 0.0005 MG/L .002 MG/L