ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0420312

Federal Type:

NP

Water System Name:

AMPHITHEATER HALOWAY EAST

Primary Source:

GW

Principal County Served:

PIMA

System Status:

I

Comments:

Activity Date:

1999-06-17



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
072694-32 1005 ARSENIC 1994-07-26 EPDS001 < MRL 0.003 MG/L .01 MG/L
072694-32 1094 ASBESTOS 1994-07-26 EPDS001 < MRL 0.198 MFL 7 MFL
072694-32 1010 BARIUM 1994-07-26 EPDS001 .091  MG/L 2 MG/L
072694-32 1015 CADMIUM 1994-07-26 EPDS001 < MRL 0.0005 MG/L .005 MG/L
072694-32 1020 CHROMIUM 1994-07-26 EPDS001 < MRL 0.005 MG/L .1 MG/L
072694-32 1035 MERCURY 1994-07-26 EPDS001 < MRL 0.0002 MG/L .002 MG/L
072694-32 1040 NITRATE 1994-07-26 EPDS001 2.97  MG/L 10 MG/L
072694-32 1038 NITRATE-NITRITE 1994-07-26 EPDS001 2.97  MG/L 10 MG/L
072694-32 1041 NITRITE 1994-07-26 EPDS001 < MRL 0.05 MG/L 1 MG/L
072694-32 1045 SELENIUM 1994-07-26 EPDS001 < MRL 0.003 MG/L .05 MG/L
072694-32 2991 TOLUENE 1994-07-26 EPDS001 < MRL 0.0005 MG/L 1 MG/L