ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0415497

Federal Type:

C

Water System Name:

EHRENBERG IMPROVEMENT DISTRICT

Primary Source:

SW

Principal County Served:

LA PAZ

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
94-06-73670 1005 ARSENIC 1994-06-08 EPDS001 < MRL 0.006 MG/L .01 MG/L
94-06-73670 1010 BARIUM 1994-06-08 EPDS001 .2  MG/L 2 MG/L
94-06-73670 1015 CADMIUM 1994-06-08 EPDS001 < MRL 0.005 MG/L .005 MG/L
94-06-73670 1017 CHLORIDE 1994-06-08 EPDS001 136  MG/L 250 MG/L
94-06-73670 1020 CHROMIUM 1994-06-08 EPDS001 < MRL 0.01 MG/L .1 MG/L
94-06-73670 1022 COPPER, FREE 1994-06-08 EPDS001 .051  MG/L 1.3 MG/L
94-06-73670 1025 FLUORIDE 1994-06-08 EPDS001 .31  MG/L 4 MG/L
94-06-73670 1028 IRON 1994-06-08 EPDS001 .01  MG/L .3 MG/L
94-06-73670 1030 LEAD 1994-06-08 EPDS001 < MRL 0.001 MG/L
94-06-73670 1032 MANGANESE 1994-06-08 EPDS001 .01  MG/L .05 MG/L
94-06-73670 1035 MERCURY 1994-06-08 EPDS001 < MRL 0.001 MG/L .002 MG/L
94-06-73670 1040 NITRATE 1994-06-08 EPDS001 .15  MG/L 10 MG/L
94-06-73670 1038 NITRATE-NITRITE 1994-06-08 EPDS001 .24  MG/L 10 MG/L
94-06-73670 1041 NITRITE 1994-06-08 EPDS001 .09  MG/L 1 MG/L
94-06-73670 1045 SELENIUM 1994-06-08 EPDS001 < MRL 0.01 MG/L .05 MG/L
94-06-73670 1050 SILVER 1994-06-08 EPDS001 < MRL 0.01 MG/L .1 MG/L
94-06-73670 1052 SODIUM 1994-06-08 EPDS001 63  MG/L 3000 MG/L
94-06-73670 1055 SULFATE 1994-06-08 EPDS001 422  MG/L 250 MG/L
94-06-73670 1095 ZINC 1994-06-08 EPDS001 < MRL 0.01 MG/L 5 MG/L