ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0415023

Federal Type:

C

Water System Name:

WENDEN DWID

Primary Source:

GW

Principal County Served:

LA PAZ

System Status:

A - MAP

Comments:

Activity Date:

1977-06-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
202105260128I 1074 ANTIMONY, TOTAL 2021-05-25 EPDS001 < MRL 1 UG/L .006 MG/L 2021-01-01
2023-12-31
202105260128I 1005 ARSENIC 2021-05-25 EPDS001 9.4  UG/L .01 MG/L 2021-04-01
2021-06-30
202105260128I 1010 BARIUM 2021-05-25 EPDS001 4.2  UG/L 2 MG/L 2021-01-01
2023-12-31
202105260128I 1075 BERYLLIUM, TOTAL 2021-05-25 EPDS001 < MRL 1 UG/L .004 MG/L 2021-01-01
2023-12-31
202105260128I 1015 CADMIUM 2021-05-25 EPDS001 < MRL 0.5 UG/L .005 MG/L 2021-01-01
2023-12-31
202105260128I 1020 CHROMIUM 2021-05-25 EPDS001 38  UG/L .1 MG/L 2021-01-01
2023-12-31
202105260128I 1024 CYANIDE 2021-05-25 EPDS001 < MRL 0.025 MG/L .2 MG/L 2021-01-01
2023-12-31
202105260128I 1025 FLUORIDE 2021-05-25 EPDS001 3  MG/L 4 MG/L 2021-01-01
2023-12-31
202105260128I 1035 MERCURY 2021-05-25 EPDS001 < MRL 0.2 UG/L .002 MG/L 2021-01-01
2023-12-31
202105260128I 1036 NICKEL 2021-05-25 EPDS001 < MRL 5 UG/L 2021-01-01
2023-12-31
202105260128I 1040 NITRATE 2021-05-25 EPDS001 2.8  MG/L 10 MG/L 2021-01-01
2021-12-31
202105260128I 1045 SELENIUM 2021-05-25 EPDS001 < MRL 5 UG/L .05 MG/L 2021-01-01
2023-12-31
202105260128I 1052 SODIUM 2021-05-25 EPDS001 130  MG/L 3000 MG/L 2021-01-01
2023-12-31
202105260128I 1085 THALLIUM, TOTAL 2021-05-25 EPDS001 < MRL 1 UG/L .002 MG/L 2021-01-01
2023-12-31