ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0415016

Federal Type:

NC

Water System Name:

ADOT BOUSE WASH REST AREA

Primary Source:

GW

Principal County Served:

LA PAZ

System Status:

A

Comments:

Activity Date:

2010-09-27



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
44724X 1005 ARSENIC 1995-09-13 EPDS001 < MRL 0.01 MG/L .01 MG/L
44724X 1010 BARIUM 1995-09-13 EPDS001 < MRL 0.1 MG/L 2 MG/L
44724X 1015 CADMIUM 1995-09-13 EPDS001 < MRL 0.001 MG/L .005 MG/L
44724X 1017 CHLORIDE 1995-09-13 EPDS001 197  MG/L 250 MG/L
44724X 1020 CHROMIUM 1995-09-13 EPDS001 < MRL 0.01 MG/L .1 MG/L
44724X 1022 COPPER, FREE 1995-09-13 EPDS001 < MRL 0.01 MG/L 1.3 MG/L
44724X 1025 FLUORIDE 1995-09-13 EPDS001 3.6  MG/L 4 MG/L
44724X 1028 IRON 1995-09-13 EPDS001 < MRL 0.1 MG/L .3 MG/L
44724X 1030 LEAD 1995-09-13 EPDS001 .005  MG/L
44724X 1032 MANGANESE 1995-09-13 EPDS001 < MRL 0.05 MG/L .05 MG/L
44724X 1035 MERCURY 1995-09-13 EPDS001 < MRL 0.0005 MG/L .002 MG/L
44724X 1040 NITRATE 1995-09-13 EPDS001 5.54  MG/L 10 MG/L
44724X 1038 NITRATE-NITRITE 1995-09-13 EPDS001 5.54  MG/L 10 MG/L
44724X 1041 NITRITE 1995-09-13 EPDS001 < MRL 0.1 MG/L 1 MG/L
44724X 1045 SELENIUM 1995-09-13 EPDS001 < MRL 0.005 MG/L .05 MG/L
44724X 1050 SILVER 1995-09-13 EPDS001 < MRL 0.001 MG/L .1 MG/L
44724X 1052 SODIUM 1995-09-13 EPDS001 262  MG/L 3000 MG/L
44724X 1055 SULFATE 1995-09-13 EPDS001 374  MG/L 250 MG/L
44724X 1095 ZINC 1995-09-13 EPDS001 .09  MG/L 5 MG/L