ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0414103

Federal Type:

NTNC

Water System Name:

YUMA DESALTING PROJECT

Primary Source:

SW

Principal County Served:

YUMA

System Status:

A

Comments:

Activity Date:

1994-09-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
2004040022I 1074 ANTIMONY, TOTAL 2000-03-31 EPDS001 < MRL 0.001 MG/L .006 MG/L
2004040022I 1005 ARSENIC 2000-03-31 EPDS001 .0012  MG/L .01 MG/L
2004040022I 1010 BARIUM 2000-03-31 EPDS001 .015  MG/L 2 MG/L
2004040022I 1075 BERYLLIUM, TOTAL 2000-03-31 EPDS001 < MRL 0.001 MG/L .004 MG/L
2004040022I 1015 CADMIUM 2000-03-31 EPDS001 < MRL 0.0005 MG/L .005 MG/L
2004040022I 1020 CHROMIUM 2000-03-31 EPDS001 < MRL 0.002 MG/L .1 MG/L
2004040022I 1035 MERCURY 2000-03-31 EPDS001 < MRL 0.0002 MG/L .002 MG/L
2004040022I 1036 NICKEL 2000-03-31 EPDS001 < MRL 0.005 MG/L
2004040022I 1045 SELENIUM 2000-03-31 EPDS001 < MRL 0.005 MG/L .05 MG/L
2004040022I 1052 SODIUM 2000-03-31 EPDS001 210  MG/L 3000 MG/L
2004040022I 1085 THALLIUM, TOTAL 2000-03-31 EPDS001 < MRL 0.001 MG/L .002 MG/L