2017062903881 1074 ANTIMONY, TOTAL 2017-06-28 EPDS001 < MRL 0.001 MG/L .006 MG/L 2017-01-01
2017-12-31
2017062903881 1005 ARSENIC 2017-06-28 EPDS001 0.0014  MG/L .01 MG/L 2017-01-01
2017-12-31
2017062903881 1010 BARIUM 2017-06-28 EPDS001 0.079  MG/L 2 MG/L 2017-01-01
2017-12-31
2017062903881 1075 BERYLLIUM, TOTAL 2017-06-28 EPDS001 < MRL 0.001 MG/L .004 MG/L 2017-01-01
2017-12-31
2017062903881 1015 CADMIUM 2017-06-28 EPDS001 < MRL 0.0005 MG/L .005 MG/L 2017-01-01
2017-12-31
2017062903881 1020 CHROMIUM 2017-06-28 EPDS001 < MRL 0.001 MG/L .1 MG/L 2017-01-01
2017-12-31
2017062903881 1024 CYANIDE 2017-06-28 EPDS001 < MRL 0.0005 MG/L .2 MG/L 2017-01-01
2017-12-31
2017062903881 1025 FLUORIDE 2017-06-28 EPDS001 0.62  MG/L 4 MG/L 2017-01-01
2017-12-31
2017062903881 1035 MERCURY 2017-06-28 EPDS001 < MRL 0.0002 MG/L .002 MG/L 2017-01-01
2017-12-31
2017062903881 1036 NICKEL 2017-06-28 EPDS001 < MRL 0.005 MG/L 2017-01-01
2017-12-31
2017062903881 1040 NITRATE 2017-06-28 EPDS001 1.8  MG/L 10 MG/L 2017-01-01
2017-12-31
2017062903881 1038 NITRATE-NITRITE 2017-06-28 EPDS001 1.8  MG/L 10 MG/L
2017062903881 1041 NITRITE 2017-06-28 EPDS001 < MRL 0.05 MG/L 1 MG/L 2012-01-01
2020-12-31
2017062903881 1045 SELENIUM 2017-06-28 EPDS001 < MRL 0.005 MG/L .05 MG/L 2017-01-01
2017-12-31
2017062903881 1052 SODIUM 2017-06-28 EPDS001 220  MG/L 3000 MG/L 2017-01-01
2017-12-31
2017062903881 1085 THALLIUM, TOTAL 2017-06-28 EPDS001 < MDL 0.001 MG/L .002 MG/L 2017-01-01