ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0414082

Federal Type:

C

Water System Name:

USMC YUMA MAIN SYSTEM

Primary Source:

SW

Principal County Served:

YUMA

System Status:

A

Comments:

Activity Date:

1979-01-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
12A0480-01(2I) 1074 ANTIMONY, TOTAL 2012-01-17 EPDS001 < MRL 0.0005 MG/L .006 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1005 ARSENIC 2012-01-17 EPDS001 0.0029  MG/L .01 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1010 BARIUM 2012-01-17 EPDS001 < MRL 0.05 MG/L 2 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1075 BERYLLIUM, TOTAL 2012-01-17 EPDS001 < MRL 0.002 MG/L .004 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1015 CADMIUM 2012-01-17 EPDS001 < MRL 0.002 MG/L .005 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1020 CHROMIUM 2012-01-17 EPDS001 < MRL 0.03 MG/L .1 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1024 CYANIDE 2012-01-17 EPDS001 < MRL 0.1 MG/L .2 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1025 FLUORIDE 2012-01-17 EPDS001 < MRL 0.5 MG/L 4 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1035 MERCURY 2012-01-17 EPDS001 < MRL 0.001 MG/L .002 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1036 NICKEL 2012-01-17 EPDS001 < MRL 0.05 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1040 NITRATE 2012-01-17 EPDS001 2.8  MG/L 10 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1038 NITRATE-NITRITE 2012-01-17 EPDS001 2.8  MG/L 10 MG/L
12A0480-01(2I) 1041 NITRITE 2012-01-17 EPDS001 < MRL 0.1 MG/L 1 MG/L 2012-01-01
2020-12-31
12A0480-01(2I) 1045 SELENIUM 2012-01-17 EPDS001 0.0051  MG/L .05 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1052 SODIUM 2012-01-17 EPDS001 320  MG/L 3000 MG/L 2012-01-01
2012-12-31
12A0480-01(2I) 1085 THALLIUM, TOTAL 2012-01-17 EPDS001 < MRL 0.0005 MG/L .002 MG/L 2012-01-01
2012-12-31