ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0414032

Federal Type:

NP

Water System Name:

DATELAND WATER LLC

Primary Source:

GW

Principal County Served:

YUMA

System Status:

I

Comments:

Activity Date:

2018-11-14



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
2612210208I 1074 ANTIMONY, TOTAL 2006-12-20 EPDS001 < MRL 0.001 MG/L .006 MG/L 2003-01-01
2011-12-31
2612210208I 1005 ARSENIC 2006-12-20 EPDS001 .028  MG/L .01 MG/L
2612210208I 1010 BARIUM 2006-12-20 EPDS001 .0055  MG/L 2 MG/L 2003-01-01
2011-12-31
2612210208I 1075 BERYLLIUM, TOTAL 2006-12-20 EPDS001 < MRL 0.004 MG/L .004 MG/L 2003-01-01
2011-12-31
2612210208I 1015 CADMIUM 2006-12-20 EPDS001 < MRL 0.0005 MG/L .005 MG/L 2003-01-01
2011-12-31
2612210208I 1020 CHROMIUM 2006-12-20 EPDS001 .0086  MG/L .1 MG/L 2003-01-01
2011-12-31
2612210208I 1024 CYANIDE 2006-12-20 EPDS001 < MRL 0.03 MG/L .2 MG/L 2003-01-01
2011-12-31
2612210208I 1025 FLUORIDE 2006-12-20 EPDS001 5.9  MG/L 4 MG/L
2612210208I 1035 MERCURY 2006-12-20 EPDS001 < MRL 0.0002 MG/L .002 MG/L 2003-01-01
2011-12-31
2612210208I 1036 NICKEL 2006-12-20 EPDS001 < MRL 0.005 MG/L 2003-01-01
2011-12-31
2612210208I 1045 SELENIUM 2006-12-20 EPDS001 < MRL 0.005 MG/L .05 MG/L 2003-01-01
2011-12-31
2612210208I 1052 SODIUM 2006-12-20 EPDS001 450  MG/L 3000 MG/L 2003-01-01
2011-12-31
2612210208I 1085 THALLIUM, TOTAL 2006-12-20 EPDS001 < MRL 0.001 MG/L .002 MG/L 2003-01-01
2011-12-31