ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0413470

Federal Type:

NP

Water System Name:

PRESCOTT MOBILE HOME ESTA

Primary Source:

GW

Principal County Served:

YAVAPAI

System Status:

I

Comments:

Activity Date:

2003-08-22



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
93WA14097 1005 ARSENIC 1993-11-02 EPDS001 .022  MG/L .01 MG/L
93WA14097 1010 BARIUM 1993-11-02 EPDS001 .14  MG/L 2 MG/L
93WA14097 1015 CADMIUM 1993-11-02 EPDS001 < MRL 0.005 MG/L .005 MG/L
93WA14097 1017 CHLORIDE 1993-11-02 EPDS001 36  MG/L 250 MG/L
93WA14097 1020 CHROMIUM 1993-11-02 EPDS001 < MRL 0.01 MG/L .1 MG/L
93WA14097 1022 COPPER, FREE 1993-11-02 EPDS001 .08  MG/L 1.3 MG/L
93WA14097 1025 FLUORIDE 1993-11-02 EPDS001 .21  MG/L 4 MG/L
93WA14097 1028 IRON 1993-11-02 EPDS001 .1  MG/L .3 MG/L
93WA14097 1030 LEAD 1993-11-02 EPDS001 .009  MG/L
93WA14097 1032 MANGANESE 1993-11-02 EPDS001 < MRL 0.01 MG/L .05 MG/L
93WA14097 1035 MERCURY 1993-11-02 EPDS001 < MRL 0.001 MG/L .002 MG/L
93WA14097 1040 NITRATE 1993-11-02 EPDS001 6.12  MG/L 10 MG/L
93WA14097 1041 NITRITE 1993-11-02 EPDS001 1.74  MG/L 1 MG/L
93WA14097 1045 SELENIUM 1993-11-02 EPDS001 < MRL 0.005 MG/L .05 MG/L
93WA14097 1050 SILVER 1993-11-02 EPDS001 < MRL 0.01 MG/L .1 MG/L
93WA14097 1052 SODIUM 1993-11-02 EPDS001 29.4  MG/L 3000 MG/L
93WA14097 1055 SULFATE 1993-11-02 EPDS001 27  MG/L 250 MG/L
93WA14097 1095 ZINC 1993-11-02 EPDS001 .37  MG/L 5 MG/L