ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0413045

Federal Type:

C

Water System Name:

PRESCOTT CITY OF

Primary Source:

GW

Principal County Served:

YAVAPAI

System Status:

A

Comments:

Activity Date:

1978-03-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
22A3003-01IOC 1074 ANTIMONY, TOTAL 2022-01-25 EPDS013 0.0008  MG/L .006 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1005 ARSENIC 2022-01-25 EPDS013 0.003  MG/L .01 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1010 BARIUM 2022-01-25 EPDS013 0.036  MG/L 2 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1075 BERYLLIUM, TOTAL 2022-01-25 EPDS013 < MDL 0.002 MG/L .004 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1015 CADMIUM 2022-01-25 EPDS013 < MRL 0.0001 MG/L .005 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1020 CHROMIUM 2022-01-25 EPDS013 < MRL 0.005 MG/L .1 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1024 CYANIDE 2022-01-25 EPDS013 < MRL 0.01 MG/L .2 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1025 FLUORIDE 2022-01-25 EPDS013 0.29  MG/L 4 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1035 MERCURY 2022-01-25 EPDS013 < MRL 0.0002 MG/L .002 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1036 NICKEL 2022-01-25 EPDS013 < MRL 0.02 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1040 NITRATE 2022-01-25 EPDS013 2.02  MG/L 10 MG/L 2022-01-01
2022-12-31
22A3003-01IOC 1045 SELENIUM 2022-01-25 EPDS013 < MRL 0.002 MG/L .05 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1052 SODIUM 2022-01-25 EPDS013 14  MG/L 3000 MG/L 2022-01-01
2024-12-31
22A3003-01IOC 1085 THALLIUM, TOTAL 2022-01-25 EPDS013 < MRL 0.0005 MG/L .002 MG/L 2022-01-01
2024-12-31