ADEQ - HOME SAFE DRINKING WATER WATER SYSTEM SEARCH


Water System Detail Information

Water System No.:

AZ0413039

Federal Type:

C

Water System Name:

MAYER DWID

Primary Source:

GW

Principal County Served:

YAVAPAI

System Status:

A - MAP

Comments:

Activity Date:

1978-03-01



Sample
Number
Analyte
Code
Analyte
Name
Date Sample Point Less
Than
Ind.
Level
Type
Reporting
Level
Concentration MCL Compliance Monitoring Period
380-81134-2 1074 ANTIMONY, TOTAL 2024-01-31 EPDS011 < MRL 1 UG/L .006 MG/L 2024-01-01
2032-12-31
380-81134-2 1005 ARSENIC 2024-01-31 EPDS011 1.4  UG/L .01 MG/L 2024-01-01
2024-03-31
380-81134-2 1010 BARIUM 2024-01-31 EPDS011 6.9  UG/L 2 MG/L 2024-01-01
2032-12-31
380-81134-2 1075 BERYLLIUM, TOTAL 2024-01-31 EPDS011 < MRL 1 UG/L .004 MG/L 2024-01-01
2032-12-31
380-81134-2 1015 CADMIUM 2024-01-31 EPDS011 < MRL 0.5 UG/L .005 MG/L 2024-01-01
2032-12-31
380-81134-2 1020 CHROMIUM 2024-01-31 EPDS011 < MRL 1 UG/L .1 MG/L 2024-01-01
2032-12-31
380-81134-2 1024 CYANIDE 2024-01-31 EPDS011 < MRL 0.025 MG/L .2 MG/L 2024-01-01
2032-12-31
380-81134-2 1025 FLUORIDE 2024-01-31 EPDS011 0.19  MG/L 4 MG/L 2024-01-01
2032-12-31
380-81134-2 1035 MERCURY 2024-01-31 EPDS011 < MRL 0.2 UG/L .002 MG/L 2024-01-01
2032-12-31
380-81134-2 1036 NICKEL 2024-01-31 EPDS011 < MRL 5 UG/L 2024-01-01
2032-12-31
380-81134-2 1040 NITRATE 2024-01-31 EPDS011 0.41  MG/L 10 MG/L 2024-01-01
2024-12-31
380-81134-2 1045 SELENIUM 2024-01-31 EPDS011 < MRL 5 UG/L .05 MG/L 2024-01-01
2032-12-31
380-81134-2 1052 SODIUM 2024-01-31 EPDS011 29  MG/L 3000 MG/L 2024-01-01
2026-12-31
380-81134-2 1085 THALLIUM, TOTAL 2024-01-31 EPDS011 < MRL 1 UG/L .002 MG/L 2024-01-01
2032-12-31